					 Width  | 
				
					 6.2 mm  | 
			
| 
					 Height  | 
				
					 93.1 mm  | 
			
| 
					 Depth  | 
				
					 102.5 mm  | 
			
| 
					 Ambient temperature (operation)  | 
				
					 -20 °C ... 60 °C  | 
			
| 
					 Ambient temperature (storage/transport)  | 
				
					 -40 °C ... 85 °C  | 
			
| 
					 Permissible humidity (operation)  | 
				
					 10 % ... 95 % (non-condensing)  | 
			
| 
					 Degree of protection  | 
				
					 IP20  | 
			
| 
					 Noise immunity  | 
				
					 EN 61000-6-2 When being exposed to interference, there may be minimal deviations.  | 
			
| 
					 Number of inputs  | 
				
					 1  | 
			
| 
					 Configurable/programmable  | 
				
					 Yes, unconfigured  | 
			
| 
					 Voltage input signal  | 
				
					 0 V ... 10 V (please indicate if different setting when ordering)  | 
			
| 
					 1 V ... 5 V  | 
			|
| 
					 Current input signal  | 
				
					 0 mA ... 20 mA  | 
			
| 
					 4 mA ... 20 mA  | 
			|
| 
					 max. input voltage  | 
				
					 30 V  | 
			
| 
					 Max. input current  | 
				
					 50 mA  | 
			
| 
					 Input resistance of voltage input  | 
				
					 approx. 100 kΩ  | 
			
| 
					 Input resistance current input  | 
				
					 approx. 50 Ω  | 
			
| 
					 Number of outputs  | 
				
					 2  | 
			
| 
					 Configurable/programmable  | 
				
					 Yes, unconfigured  | 
			
| 
					 Current output signal  | 
				
					 2x 0 mA ... 20 mA  | 
			
| 
					 2x 4 mA ... 20 mA  | 
			|
| 
					 Max. output current  | 
				
					 approx. 22 mA  | 
			
| 
					 Load/output load current output  | 
				
					 ≤ 250 Ω (at 20 mA)  | 
			
| 
					 Ripple  | 
				
					 < 20 mVPP (at 250 Ω)  | 
			
| 
					 Nominal supply voltage  | 
				
					 24 V DC  | 
			
| 
					 Supply voltage range  | 
				
					 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))  | 
			
| 
					 Max. current consumption  | 
				
					 < 30 mA (at 24 V DC incl. load)  | 
			
| 
					 Power consumption  | 
				
					 < 600 mW  | 
			
| 
					 Connection method  | 
				
					 Screw connection  | 
			
| 
					 Stripping length  | 
				
					 12 mm  | 
			
| 
					 Screw thread  | 
				
					 M3  | 
			
| 
					 Conductor cross section solid  | 
				
					 0.2 mm² ... 2.5 mm²  | 
			
| 
					 Conductor cross section flexible  | 
				
					 0.2 mm² ... 2.5 mm²  | 
			
| 
					 Conductor cross section AWG  | 
				
					 26 ... 12  | 
			
| 
					 No. of channels  | 
				
					 2  | 
			
| 
					 Maximum transmission error  | 
				
					 ≤ 0.2 % (of final value)  | 
			
| 
					 Transmission error, typical  | 
				
					 < 0.1 %  | 
			
| 
					 Maximum temperature coefficient  | 
				
					 < 0.01 %/K  | 
			
| 
					 Temperature coefficient, typical  | 
				
					 < 0.004 %/K  | 
			
| 
					 Limit frequency (3 dB)  | 
				
					 approx. 35 Hz  | 
			
| 
					 Protective circuit  | 
				
					 Transient protection  | 
			
| 
					 Electrical isolation  | 
				
					 Basic insulation according to EN 61010  | 
			
| 
					 Overvoltage category  | 
				
					 II  | 
			
| 
					 Degree of pollution  | 
				
					 2  | 
			
| 
					 Rated insulation voltage  | 
				
					 50 V AC/DC  | 
			
| 
					 Test voltage, input/output/supply  | 
				
					 1.5 kV (50 Hz, 1 min.)  | 
			
| 
					 Electromagnetic compatibility  | 
				
					 Conformance with EMC directive  | 
			
| 
					 Noise emission  | 
				
					 EN 61000-6-4  | 
			
| 
					 Noise immunity  | 
				
					 EN 61000-6-2 When being exposed to interference, there may be minimal deviations.  | 
			
| 
					 Color  | 
				
					 green  | 
			
| 
					 Housing material  | 
				
					 PBT  | 
			
| 
					 Mounting position  | 
				
					 any  | 
			
| 
					 Assembly instructions  | 
				
					 The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.  | 
			
| 
					 Conformance  | 
				
					 CE-compliant  | 
			
| 
					 ATEX  | 
				
					 X II 3 G Ex nA IIC T4 Gc X  | 
			
| 
					 UL, USA/Canada  | 
				
					 UL 508 Recognized  | 
			
| 
					 Class I, Div. 2, Groups A, B, C, D T5  | 
			|
| 
					 GL  | 
				
					 GL EMC 2 D  | 
			
| 
					 Fire protection for rail vehicles (DIN EN 45545-2) R22  | 
				
					 HL 1 - HL 2  | 
			
| 
					 Fire protection for rail vehicles (DIN EN 45545-2) R23  | 
				
					 HL 1 - HL 2  | 
			
| 
					 Fire protection for rail vehicles (DIN EN 45545-2) R24  | 
				
					 HL 1 - HL 2  | 
			
| 
					 Designation  | 
				
					 Electromagnetic RF field  | 
			
| 
					 Standards/regulations  | 
				
					 EN 61000-4-3  | 
			
| 
					 Typical deviation from the measuring range final value  | 
				
					 5 %  | 
			
| 
					 Designation  | 
				
					 Fast transients (burst)  | 
			
| 
					 Standards/regulations  | 
				
					 EN 61000-4-4  | 
			
| 
					 Typical deviation from the measuring range final value  | 
				
					 5 %  | 
			
| 
					 Designation  | 
				
					 Conducted interferences  | 
			
| 
					 Standards/regulations  | 
				
					 EN 61000-4-6  | 
			
| 
					 Typical deviation from the measuring range final value  | 
				
					 5 %  | 
			
| 
					 Electromagnetic compatibility  | 
				
					 Conformance with EMC directive  | 
			
| 
					 Noise emission  | 
				
					 EN 61000-6-4  | 
			
| 
					 Connection in acc. with standard  | 
				
					 CUL  | 
			
| 
					 Standards/regulations  | 
				
					 EN 61000-4-2  | 
			
| 
					 Designation  | 
				
					 Electromagnetic RF field  | 
			
| 
					 Standards/regulations  | 
				
					 EN 61000-4-3  | 
			
| 
					 EN 61000-4-4  | 
			|
| 
					 EN 61000-4-5  | 
			|
| 
					 Designation  | 
				
					 Conducted interferences  | 
			
| 
					 Standards/regulations  | 
				
					 EN 61000-4-6  | 
			
| 
					 Electrical isolation  | 
				
					 Basic insulation according to EN 61010  | 
			
| 
					 Conformance  | 
				
					 CE-compliant  | 
			
| 
					 ATEX  | 
				
					 X II 3 G Ex nA IIC T4 Gc X  | 
			
| 
					 UL, USA/Canada  | 
				
					 UL 508 Recognized  | 
			
| 
					 Class I, Div. 2, Groups A, B, C, D T5  | 
			|
| 
					 GL  | 
				
					 GL EMC 2 D  | 
			
| 
					 Fire protection for rail vehicles (DIN EN 45545-2) R22  | 
				
					 HL 1 - HL 2  | 
			
| 
					 Fire protection for rail vehicles (DIN EN 45545-2) R23  | 
				
					 HL 1 - HL 2  | 
			
| 
					 Fire protection for rail vehicles (DIN EN 45545-2) R24  | 
				
					 HL 1 - HL 2  | 
			
| 
					 China RoHS  | 
				
					 Environmentally Friendly Use Period = 50  | 
			
| 
					 For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”  | 
			
| 
					 eCl@ss 4.0  | 
				
					 27210100  | 
			
| 
					 eCl@ss 4.1  | 
				
					 27210100  | 
			
| 
					 eCl@ss 5.0  | 
				
					 27210100  | 
			
| 
					 eCl@ss 5.1  | 
				
					 27210100  | 
			
| 
					 eCl@ss 6.0  | 
				
					 27210100  | 
			
| 
					 eCl@ss 7.0  | 
				
					 27210120  | 
			
| 
					 eCl@ss 8.0  | 
				
					 27210120  | 
			
| 
					 eCl@ss 9.0  | 
				
					 27210120  | 
			
| 
					 ETIM 4.0  | 
				
					 EC002653  | 
			
| 
					 ETIM 5.0  | 
				
					 EC002653  | 
			
| 
					 ETIM 6.0  | 
				
					 EC002653  | 
			
| 
					 ETIM 7.0  | 
				
					 EC002653  | 
			
| 
					 UNSPSC 6.01  | 
				
					 30211506  | 
			
| 
					 UNSPSC 7.0901  | 
				
					 39121008  | 
			
| 
					 UNSPSC 11  | 
				
					 39121008  | 
			
| 
					 UNSPSC 12.01  | 
				
					 39121008  | 
			
| 
					 UNSPSC 13.2  | 
				
					 39121008  |